Guangdong Zecheng Intelligent Technology Co., Ltd

quentin@zecheng.com.cn

86-0769-39020536

होम> ब्लॉग> Installation Access Control System Frequently Asked Questions

Installation Access Control System Frequently Asked Questions

January 18, 2023
During installation and commissioning, attention should be paid to the following aspects:

First, power:

Ensure sufficient power, try to use a linear power supply, door locks and controllers should be powered separately. Install the power supply as close as possible to the electrical equipment to avoid interference and transmission loss.

Second, wiring:

Divided into power lines, communication lines, signal lines, pay attention to strong, weak separation of wiring, two pipes separated by more than 20cm.

Power cord: The wire is thick enough to use multiple wires.

Signal and communication lines: Shielded Category 5 twisted pair cable. The 485 bus must use a twisted pair of wire connections. It is recommended to use 4*0.5 four-core shielded cable when purchasing the wire.

Note the following points:

1. The shielded cable must not be used as a connection line of 0V voltage (power ground). 2. Only one grounding terminal of each shielded circuit can be used. 3. When the shielded loop cannot be grounded, the shielded cable can be connected to another one of the networks. Shielded circuit.

4. The signal ground of each module must be connected together.

5. If there is a breakpoint in the middle of the line, the breakpoint must be soldered and insulated.

6, do not put the network cable and AC power together.

7. If the network connection exceeds 1000 meters, repeaters must be added and the repeater can be extended for another 1000 meters.

Third, the access control system:

Pay attention to the selection of the installation location to prevent electromagnetic interference.

1. Card reader: Do not install on a metal object. The distance between the two readers should not be less than 30 cm. It is best to supply power through the controller. If the reader is powered separately from the outside, use a linear regulator (transformer) for the card reader power supply, and do not connect the negative terminal of the DC to the AC ground.

2. Network adapter: The connection between the controller and the controller adopts a hand-in-hand approach.

3, controller: without isolation controller, it is recommended to use the same power supply.

4, lock: Shenzhen Anderson magnetic lock manufacturers, in the installation of magnetic locks, we must make the lock body and the iron plate can be closely combined, otherwise there will be insufficient suction. Electric plug lock, if you need to open the jack when installing the electric plug lock, pay attention to the aperture must be large enough, the depth must be deep enough, so that the bolt can be fully inserted. The lock tongue cannot be fully inserted. After the door is locked, the lock tongue constantly jumps or the working current is always great and the lock body is hot.
संपर्क करें

Author:

Ms. Yanjun Chen

ईमेल:

quentin@zecheng.com.cn

Phone/WhatsApp:

+8613602572892

लोकप्रिय उत्पाद
You may also like
Related Categories

इस आपूर्तिकर्ता को ईमेल

विषय:
ईमेल:
संदेश:

Your message must be betwwen 20-8000 characters

होम

Product

Phone

हमारे बारे में

जांच

We will contact you immediately

Fill in more information so that we can get in touch with you faster

Privacy statement: Your privacy is very important to Us. Our company promises not to disclose your personal information to any external company with out your explicit permission.

भेजें